Honeywell 2106B1307 Signalpoint CO 0-500 ppm Toxic Sensor Detector
Honeywell 2106B1307 Signalpoint CO 0-500 ppm Toxic Sensor Detector
$450.00
Price negotiable
Signalpoint Toxic 2106B1307 Signalpoint CO 0-500 ppm Toxic Sensor
Honeywell 2106B1307 Signalpoint CO 0-500 ppm Toxic Sensor Detector
The Signalpoint range of flammable, toxic and oxygen gas detectors offer users a low cost solution to their indoor gas monitoring needs. Supplied with an integral pre-wired junction box with local LED
indicator (toxic only), the detector can be installed using conduit or cable and glands depending on
individual site standards.
Two types are provided. Flammable detectors offer mV bridge output for use with dedicated gas control systems (such as Unipoint, TouchPoint & System 57) and are certified under ATEX for use in potentially explosive atmospheres. Toxic and oxygen detectors are designed for use in non explosive atmospheres.They are 2 wire 4-20mA loop powered and can be used with the above-mentioned gas control systems or with a PLC
Signalpoint Toxic
2106B1307 Signalpoint CO 0-500 ppm Toxic Sensor
The Signalpoint range of flammable, toxic and Oxygen gas detectors offers a low cost solution to indoor gas monitoring.
Features & Benefits
- Flammable, toxic and Oxygen versions available
- ATEX hazardous area approval
- Wall or ceiling mounting
Quick Specs
Sensor: Polyphenylene Sulphide (PPS). Integral Junction Box: Impact resistant Nylon.
IP54 in accordance with EN60529:1992
Product Overview
Supplied with an integral pre-wired junction box, the detector can be installed using conduit or cable and glands depending on individual site standards.
Two basic arrangements are provided. Flammable detectors offer mV bridge output for use with dedicated gas control systems (such as Unipoint) and are certified under ATEX for use in potentially explosive atmospheres. Toxic and Oxygen detectors are designed for use in non-explosive atmospheres.
They are 2 wire 4-20mA loop powered and can be used with PLC or dedicated gas control systems.
Toxic and Oxygen versions of Signalpoint also provide a local LED indication of their status; periodic green flash (OK), flashing amber (warning) and flashing red (alarm). Seconds count and so the front-end sensor design ensures fast speed of response even with ‘sticky’ gases.
Easy installation is provided for. The junction box includes ‘hidden’ mounting for
wall and ceiling fixings. The hinged lid of the junction box ensures both hands
are free to complete electrical connections via the M20 clearance cable/conduit entry.
Maintenance requirements are kept simple and to a minimum. Normally used with the Honeywell Analytics range of industrial controllers, all user adjustments are made at the controller as required. At the end of their operating life, simply replace the sensor before re-configuring the controller. Sensor exchange kits are available to replace the electrochemical sensors used in the toxic and Oxygen detectors. The flammable sensor is simply replaced by fitting a new lid complete with sensing element.
Signalpoint offers low cost, easy installation and simple maintenance. As part of any Honeywell Analytics gas detection system you are assured of being surrounded by gas detection equipment you can trust to keep you safe.
Additional Features and Benefits:
One-Stop Shop
• Flammable, toxic and Oxygen versions available
• IP54 as standard
• Suitable for indoor use
Proven Sensor Technology
• Surecell™ electrochemical sensors
• Poison resistant catalytic bead
• Fast and reliable
Combustible Version
• ATEX hazardous area approval
• Performance to EN50054
• Typical 5 year operational life
Toxic and Oxygen Versions
• Indoor non hazardous area use
• Local LED indication of status (operation, A1 and A2)
• Performance to EN45544*
• Typical 2 year operational life * H2S version only
Easy to Use
• Factory set operation
• Simple to replace sensors
• Minimal training required
Friendly Installation
• Wall or ceiling mounting
• Integral junction box
• Pre-drilled M20 clearance cable entry
Range of Accessories
• Weather Housing
• Flow adaptor
• Duct mounting kit
• Collecting cone
* Oxygen detection products must only be used to detect Oxygen depletion in air.
Additional information
Material | Sensor: Polyphenylene Sulphide (PPS). Integral Junction Box: Impact resistant Nylon. |
---|---|
Weight | 495g (17.4oz) |
Applicable Standards | EMC to EN50270 |